Technical Specification
- Capacity (Kg)- 2,3 & 4,5
- Type of Extinguisher- Co2 type
- Type of Extinguisher Media- Co2 gas
- Minimum Effective Discharge (%)-95
- Minimum Discharge Time (Sec) 2-Not less than 13 second
- Body Tested- 250 (kgf/cm²)
- Operating Position- Upright
- 2 Charged Pressure (Kgf/cm )-15
- Operating Value-Squeeze grip type
- Expellant -Pressurized with N Gas
- Operating Temperature Range oC- (-) 10 to (+) 55
Application:
- Class B Fire: Petroleum, Oil Diesel, Paint, Varnish, Solvent, Aviation Fuel,
- Flammable and Volatile Liquids etc.
- Class C Fire: Flammable Gasses, Industrial Gasses etc.
- Electrical Fires.